11 led indicator & trouble-shooting, 1 led indicator diagnosis, Devicenet network scanner dvpdnet-sl – Delta DVP-0204520-03 User Manual
Page 42
DeviceNet Network Scanner DVPDNET-SL
11 LED Indicator & Trouble-shooting
DVPDNET-SL supports two diagnostic methods: indicator diagnosis and digital displayer diagnosis.
DVPDNET
POWER
MS
NS
11.1 LED Indicator Diagnosis
POWER LED
LED status
Indication
How to correct
Off
Power is abnormal.
Make sure DVPDNET-SL is powered.
Green light on
Power is normal.
--
NS
LED
LED status
Indication
How to correct
Off
No power or duplicate ID
check has not completed
1. Make sure DVPDNET-SL is powered.
2. Make sure at least 1 node or more are
communicating on the network.
No correction is needed; check the digital indicator for
the error.
Green light
blinking
No communication
Green light on
Normal operation
--
Red light
blinking
Error in communication
Check the digital indicator and eliminate the error.
Red light on
Network error; cannot check
duplicate ID; bus-off (check
the digital indicator)
1. Make sure all the devices have their unique node
address.
2. Check the network for correcting media installation
and baud rate.
3. Check if the node address of DVPDNET-SL is valid.
4. Check if the network power is normal.
MS
LED
LED status
Indication
How to correct
Off
No power
Make sure DVPDNET-SL is powered.
Green light
blinking
The master is not
configured.
Configure the scan list and re-download it to
DVPDNET-SL.
Green light on
Normal operation
--
Check the digital indicator and make sure the salve
information in the scan list is consistent with the salve
actually connected.
Red light
blinking
Some slaves encounter
communication error.
Red light on
Internal error
1. Check if the configuration is valid.
2. Re-power it. If the error still exists, send it back to
the factory for repair.
DVP-PLC Operation Manual
39