DeviceNet Network Scanner DVPDNET-SL

11 LED Indicator & Trouble-shooting

DVPDNET-SL supports two diagnostic methods: indicator diagnosis and digital displayer diagnosis.

DVPDNET

POWER
MS

NS

11.1 LED Indicator Diagnosis

„

POWER LED

LED status

Indication

How to correct

Off

Power is abnormal.

Make sure DVPDNET-SL is powered.

Green light on

Power is normal.

--

„

NS

LED

LED status

Indication

How to correct

Off

No power or duplicate ID
check has not completed

1. Make sure DVPDNET-SL is powered.
2. Make sure at least 1 node or more are

communicating on the network.

No correction is needed; check the digital indicator for
the error.

Green light

blinking

No communication

Green light on

Normal operation

--

Red light

blinking

Error in communication

Check the digital indicator and eliminate the error.

Red light on

Network error; cannot check
duplicate ID; bus-off (check
the digital indicator)

1. Make sure all the devices have their unique node

address.

2. Check the network for correcting media installation

and baud rate.

3. Check if the node address of DVPDNET-SL is valid.
4. Check if the network power is normal.

„

MS

LED

LED status

Indication

How to correct

Off

No power

Make sure DVPDNET-SL is powered.

Green light

blinking

The master is not
configured.

Configure the scan list and re-download it to
DVPDNET-SL.

Green light on

Normal operation

--
Check the digital indicator and make sure the salve

information in the scan list is consistent with the salve
actually connected.

Red light

blinking

Some slaves encounter
communication error.

Red light on

Internal error

1. Check if the configuration is valid.
2. Re-power it. If the error still exists, send it back to

the factory for repair.

DVP-PLC Operation Manual