beautypg.com

7 display of node status on network, 1 display of node status in scan list, 2 status of dvpdnet-sl – Delta DVP-0204520-03 User Manual

Page 26: Display of node status on network, Devicenet network scanner dvpdnet-sl

background image

DeviceNet Network Scanner DVPDNET-SL

7 Display of Node Status on Network

7.1 Display of Node Status in Scan List

This function is to monitor if DeviceNet slave is offline or not. DVPDNET-SL does read-time monitoring to the

nodes in the scan list and maps the status of every node to a bit. You can acquire the node status by

monitoring D6032 ~ D6035. See the table below for the corresponding relation between PLC devices and the

nodes on the network:

Corresponding nodes on the network

PLC

device

b15

b14

b13

b1

b0

D6032

Node 15

Node 14

Node 13

Node 1

Node 0

D6033

Node 31

Node 30

Node 29

Node 17

Node 16

D6034

Node 47

Node 46

Node 45

Node 33

Node 32

D6035

Node 63

Node 62

Node 61

Node 49

Node 48

When the node in the scan list is normal, the corresponding bit will be off. If the node occurs with abnormality,

its corresponding bit will be On.

7.2 Status of DVPDNET-SL

You can acquire the real-time status of DVPDNET-SL by monitoring D6036. When DVPDNET-SL runs

normally, D6036 = 0. When DVPDNET-SL is being initialized, the high byte of D6036 = 1 and the low byte = 0.

When error occurs in DVPDNET-SL, the high byte of D6036 = 2. For detailed error information, please refer

to the error codes, i.e. the low byte of D6036.

Explanation

PLC

device b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

D6036

Status of DVPDNET-SL

(0: normal, 1: initializing, 2: error)

Error codes of DVPDNET-SL

DVP-PLC Operation Manual

23