DeviceNet Network Scanner DVPDNET-SL

4)

Application example (I)

Target

When M0 = On, read Class 1>>Instance 1>>Attribute 1 of IFD9502

1> The

connection

DV P DNE T

DV P 28S V

RU N

S TOP

DeviceNet

RJ12

Node Address:00

Node Address:02

Note: IFD9502, a Delta DeviceNet slave module can connect VFD AC motor drive to DeviceNet network.

2> Compulsory settings and explanations on devices

„

Compulsory settings in DVPDNET-SL

Parameter

Set value

Explanation

Node address

00

Set the node address of DVPDNET-SL to “00”.
Set the communication speed of DVPDNET-SL and bus to

“500kbps”.

Baud rate

500kbps

„

Compulsory settings in DNA02

Parameter

Set value

Explanation

Node address

02

Set the node address of DNA02 to “02".
Set the communication speed of DNA02 and bus to

“500kbps”.

Baud rate

500kbps

„

Compulsory settings in VFD-B

Parameter

Set value

Explanation

02-00

04

The main frequency is operated on RS-485 interface.

02-01 03

The operation commands are operated on the
communication interface. Operation by keys is valid.

09-00

01

Communication address of VFD-B: 01

09-01

03

Baud rate: 38,400

09-04

03

Modbus RTU mode. Data format <8, N, 2>

DVP-PLC Operation Manual

17