Page 20
DeviceNet Network Scanner DVPDNET-SL
4)
Application example (I)
Target
When M0 = On, read Class 1>>Instance 1>>Attribute 1 of IFD9502
1> The
connection
DV P DNE T
DV P 28S V
RU N
S TOP
DeviceNet
RJ12
Node Address:00
Node Address:02
Note: IFD9502, a Delta DeviceNet slave module can connect VFD AC motor drive to DeviceNet network.
2> Compulsory settings and explanations on devices
Compulsory settings in DVPDNET-SL
Parameter
Set value
Explanation
Node address
00
Set the node address of DVPDNET-SL to “00”.
Set the communication speed of DVPDNET-SL and bus to
“500kbps”.
Baud rate
500kbps
Compulsory settings in DNA02
Parameter
Set value
Explanation
Node address
02
Set the node address of DNA02 to “02".
Set the communication speed of DNA02 and bus to
“500kbps”.
Baud rate
500kbps
Compulsory settings in VFD-B
Parameter
Set value
Explanation
02-00
04
The main frequency is operated on RS-485 interface.
02-01 03
The operation commands are operated on the
communication interface. Operation by keys is valid.
09-00
01
Communication address of VFD-B: 01
09-01
03
Baud rate: 38,400
09-04
03
Modbus RTU mode. Data format <8, N, 2>
DVP-PLC Operation Manual
17