4 address switch, 5 function switch, Devicenet network scanner dvpdnet-sl – Delta DVP-0204520-03 User Manual
Page 7
DeviceNet Network Scanner DVPDNET-SL
2.4 Address Switch
The switch is used on setting up the node address of DVPDNET-SL on DeviceNet. Range: 00 ~ 63 (64 ~ 99
are forbidden).
Switch setting
Content
0 … 63
Valid DeviceNet node address
64…99
Invalid DeviceNet node address
9
1
6
4
5
0
0
9
1
3
2
7
8
2
5
6
4
3
7
8
Example: If you need to set the node address of DVPDNET-SL to 26, simply switch the corresponding
switch of x10
1
to 2 and the corresponding switch of x10
0
to 6.
Note:
z
Please set up the node address when the power is switched off. After the setup is completed, re-power
DVPDNET-SL.
z
When DVPDNET-SL is operating, changing the setting of node address will be invalid.
z
Use slotted screwdriver to rotate the switch carefully in case you scratch the switch.
2.5 Function Switch
The function switches are for:
Setting up the work mode (IN0)
Setting up the baud rate of DeviceNet (DR0 ~ DR1)
DR1
DR0
Baud rate
OFF OFF
125kbps
OFF ON
250kbps
ON OFF
500kbps
ON ON
Entering the mode of extended baud rate
( see Chapter 9)
ON
When the slave is off-line, the I/O data in
the buffer area will be held.
IN0
OFF
When the slave is off-line, the I/O data in
the buffer area will be cleared.
IN1 Reserved
Note:
z
Please set up the function switch when the power is switched off. After the setup is completed, re-power
DVPDNET-SL.
z
When DVPDNET-SL is operating, changing the setting of the function switch will be invalid.
z
Use slotted screwdriver to adjust the DIP switch carefully in case you scratch the switch.
DVP-PLC Operation Manual
4