DeviceNet Network Scanner DVPDNET-SL

2.4 Address Switch

The switch is used on setting up the node address of DVPDNET-SL on DeviceNet. Range: 00 ~ 63 (64 ~ 99

are forbidden).

Switch setting

Content

0 … 63

Valid DeviceNet node address

64…99

Invalid DeviceNet node address

9

1

6

4

5

0

0

9

1

3

2

7

8

2

5

6

4

3

7

8

Example: If you need to set the node address of DVPDNET-SL to 26, simply switch the corresponding

switch of x10

1

to 2 and the corresponding switch of x10

0

to 6.

Note:

z

Please set up the node address when the power is switched off. After the setup is completed, re-power

DVPDNET-SL.

z

When DVPDNET-SL is operating, changing the setting of node address will be invalid.

z

Use slotted screwdriver to rotate the switch carefully in case you scratch the switch.

2.5 Function Switch

The function switches are for:

„

Setting up the work mode (IN0)

„

Setting up the baud rate of DeviceNet (DR0 ~ DR1)

DR1

DR0

Baud rate

OFF OFF

125kbps

OFF ON

250kbps

ON OFF

500kbps

ON ON

Entering the mode of extended baud rate
( see Chapter 9)

ON

When the slave is off-line, the I/O data in
the buffer area will be held.

IN0

OFF

When the slave is off-line, the I/O data in
the buffer area will be cleared.

IN1 Reserved

Note:

z

Please set up the function switch when the power is switched off. After the setup is completed, re-power

DVPDNET-SL.

z

When DVPDNET-SL is operating, changing the setting of the function switch will be invalid.

z

Use slotted screwdriver to adjust the DIP switch carefully in case you scratch the switch.