Devicenet network scanner dvpdnet-sl – Delta DVP-0204520-03 User Manual

Page 21

background image

DeviceNet Network Scanner DVPDNET-SL

„

Explanations on devices

Explanation

PLC device

Content

15 14 13 12 11 10 9

8

7

6

5 4 3 2 1

0

D6250 0101Hex ReqID = 01Hex

Command = 01Hex

D6251 0005Hex Port = 00Hex

Size = 05Hex

D6252 0E02Hex Service Code = 0EHex

MAC ID = 02Hex

D6253 0001Hex High bye of Class ID =00Hex Low byte of Class ID = 01Hex

D6254 0001Hex

High byte of Instance ID =
00Hex

Low byte of Instance ID =
01Hex

Request

message

editing area

D6255 0001Hex N/A

Attribute ID = 01Hex

D6000 0101Hex ReqID = 01Hex

Status = 01Hex

D6001 0002Hex Port = 00Hex

Size = 02Hex

D6002 8E02Hex Service Code = 8EHex

MAC ID = 02Hex

Response

message

editing area

D6003 031FHex

High byte of Service Data =
03Hex

Low byte of Service Data =
1FHex

3> PLC

program

MOV

H0101

D6250

M1002

ZRST

D6250

D6281

M0

MOV

H0005

D6251

MOV

H0E02

D6252

MOV

H0100

D6253

MOV

H0100

D6254

MOV

H0100

D6255

ZRST

D6000

D6031

Reset response message editing area

& request message editing area

ReqID = 01, Command = 01

Port = 00, Size = 05

Service Code = 0E, MAC ID = 02

Class ID to be read = 01

Instance ID to be read = 01

Attribute ID to be read = 01

4> Program

explanations:

„

In the beginning of the program, clear the response message editing area and request message

editing area to 0.

„

When M0 = On, DVPDNET-SL will send out request message, reading Class 1>>Instance 1>>

Attribute 1 of the target equipment (node address: 02). If the communication of explicit message is

successful, the slave will return with a response message.

„

When M0 = On, DVPDNET-SL will only send out request message once. If you would like it to send out

request message again, you will have to change ReqID.

„

When the reading is successful, the message responded from the target equipment will be stored in

D6000 ~ D6003.

DVP-PLC Operation Manual

18