Devicenet network scanner dvpdnet-sl – Delta DVP-0204520-03 User Manual
Page 19
DeviceNet Network Scanner DVPDNET-SL
2)
Structure of response message
See the table below:
Response Message
PLC device
15 14 13 12 11 10 9
8
7
6 5 4 3 2
1
0
D6000 ReqID
Status
D6001 Port
Size
D6002
Message Header
Service Code
MAC ID
D6003 ~ 6031
Message Data
Service Response Data
The definitions of ReqID, Port, Service Code and MAC ID are the same as their definitions in request
message.
Size: The length of the message, starting from D6003. Max. 58 bytes. Errors will occur when the
length is longer than 58 bytes. Unit: byte.
See the table below for the meanings of Status (status codes):
Status
Explanation
0
No explicit message is sent out.
1
The communication of explicit message is successful.
2
The explicit message is being sent out.
3
Error: No response from the target equipment.
4
Error: Command is invalid.
5
Error: Size of request message is invalid.
6
Error: Size of response message is invalid.
7
Error: Failing to establish a connection to the target equipment.
8 ~ 255
Reserved
3) Notes:
DVPDNET-SL can only send out 1 explicit message at a time.
Before sending explicit message by using WPL program, we suggest you clear the request message
editing area and response message editing area to 0.
If the slave responds with standard error code, and DVPDNET-SL also consider the communication
being successful, “The communication of explicit message is successful.” will indicate that the
communication has been completed successfully.
DVP-PLC Operation Manual