Ratings, Copper-fin i=b=r rating, Other specifications – Lochinvar COPPER-FIN 497 - 2067 User Manual
Page 8: Installation & service manual
8
Ratings
Maximum allowed working pressure is located on the rating plate.
NOTICE
Copper-fin
I=B=R Rating
Model Number
Note: Change “N” to
“L” for L.P. gas models.
Input MBH
(Note 4)
Min Max
Gross
Output
MBH
(Note 1)
Net
I=B=R
Ratings
Water,
MBH
(Note 2)
CBN497
250
495
401
349
CBN647
350
645
522
454
CBN747
350
745
603
524
CBN987
360
985
798
694
CBN1257
720
1255
1017
884
CBN1437
720
1435
1162
1010
CBN1797
720
1797
1454
1264
CBN2067
990
2065
1673
1455
Other Specifications
Boiler Water
Content
Gallons
Water
Connections
Gas
Connections
Vent Size
(Note 3)
1.7
2"
1 1/4"
6"
2.0
2"
1 1/4"
8"
2.1
2"
1 1/4"
8"
2.2
2 1/2"
2"
10"
2.6
2 1/2"
2"
12"
2.9
2 1/2"
2"
12"
3.3
2 1/2"
2"
14"
3.6
2 1/2"
2"
14"
Notes:
1. The ratings are based on standard test procedures prescribed
by the United States Department of Energy.
2. Net I=B=R ratings are based on net installed radiation of
sufficient quantity for the requirements of the building
and nothing need be added for normal piping and pickup.
Ratings are based on a piping and pickup allowance of 1.15.
3. Copper-fins require special gas venting. Use only the vent
materials and methods specified in the Installation and
Service Manual.
4. The Copper-fin is orificed for operation up to 2000
feet altitude. The ap pli ance will be derated 4% per 1000
feet above 2000 feet el e va tion. Consult the factory for
installations above 2000 feet elevation.
5. Ratings have been confirmed by AHRI.