beautypg.com

Determine unit location – Lochinvar COPPER-FIN 497 - 2067 User Manual

Page 10

background image

10

1

Determine unit location

Locating the unit

1. Maintain all clearances from combustible construction

when locating unit. See Clearances from Combustible

Construction, this page.

2. Locate the unit so that if water connections should

leak, water damage will not occur. When such locations

cannot be avoided, install a suitable drain pan that

is well-drained under the unit. The pan must not

restrict combustion air flow. The appliance

manufacturer is not responsible for water damage in

connection with this unit, or any of its components.

3.

Install indoor units so that the ignition system

components are protected from any water while

operating or during service.

4.

Appliances located in a residential garage and in

adjacent spaces that open to the garage and are not

part of the living space of a dwelling unit must be

installed so that all burners and burner ignition devices

have a minimum clearance of not less
than 18'' (46cm) above the floor. The

appliance must be located or protected so that it is

not subject to physical damage by a moving vehicle.

5. DO NOT install this appliance in any location where

gasoline or flammable vapors are likely to be present.

6. The appliance must be installed on a level surface.

7. Models 497 - 747 are approved for installation on

combustible flooring using the approved combustible floor

kits (reference Table 1A). Models 987 - 2067 are approved

for installation on combustible flooring. Do not install

appliances directly on carpeting.

8. For outdoor models, you must install an optional vent

kit. Instructions for mounting the vent kit are included

in the venting section. Do not install outdoor models

directly on the ground. You must install the outdoor

unit on a concrete, brick, block, or other

non-combustible pad. Outdoor models have additional

special location and clearance requirements. See

Outdoor Installation Venting, page 20. A wind proof

cabinet protects the unit from weather.

Indoor clearances from combustible

construction

Maintain minimum specified clearances for adequate
operation. Allow sufficient space for servicing pipe
connections, pump and other auxiliary equipment, as well
as the unit. See rating plate for specific service clearance
requirements.

Right Side

3'' (7.5 cm)

Rear

3'' (7.5 cm) (3'' min. from any surface)*

Left Side

6'' (15 cm) (24'' (0.61 m) suggested for

service)

Front

Alcove* (30'' (0.76m) suggested for service)

Top

3'' (7.5 cm)

Flue

1'' (25.4 mm)

Hot Water Pipes 1'' (25.4 mm)

*An Alcove is a closet without a door. Thirty-six inches (36")
to rear required for outdoor installation.

Note: No additional clearance is needed on the right side
of the unit for the observation port. An observation port is
located on both the right and left side of the unit.

Figure 1-1_Indoor clearances from combustible
construction

Installation

This unit meets the safe lighting performance criteria with the
gas manifold and control assembly provided, as specifi ed in the
ANSI standards for gas-fi red units. ANSI Z21.13/CSA 4.9 and
ANSI Z21.10.3/CSA 4.3.

3"
MIN
REAR

3"
MIN
RIGHT SIDE

30"
MIN
FRONT

3"
MIN
TOP

6"
MIN
LEFT SIDE

Installation & Service Manual