Water connections – Lochinvar COPPER-FIN 497 - 2067 User Manual

Page 32

background image

32

4

Water connections

Installation & Service Manual

Figure 4-6_Primary/secondary piping of multiple boilers

SECONDARY
BOILER
PUMP

FROM
SYSTEM

12" OR 4X

PIPE DIAMETERS

AIR

SEPARATOR

MAKE-UP
WATER

PRESSURE
RELIEF
VALVE

EXPANSION
TANK

LOW WATER
CUT-OFF
(OPTIONAL)

TO SYSTEM

SYSTEM
PUMP

COMMON MANIFOLD SIZE (Min.)

Models: 497 - 747

Number of Units

GPM

Diameter

(in.)

2

120

3 1/2

3

180

4

4

240

5

5

300

5

6

360

6

7

420

6

8

480

6

COMMON MANIFOLD SIZE (Min.)

Models: 987 - 2067

Number of Units

GPM

Diameter

(in.)

2

180

4

3

270

5

4

360

6

5

450

6

6

540

6

7

630

8

8

720

8

*Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.

NOTICE