beautypg.com

Water connections – Lochinvar COPPER-FIN 497 - 2067 User Manual

Page 34

background image

34

1" TEMPERATURE
AND PRESSURE
GAUGE

AUTOMATIC AIR
ELIMINATOR/VENT

SYSTEM
OUTLET

SYSTEM
SENSOR
LOCATION

SYSTEM
INLET

BUFFER
TANK

DRAIN

PUMP

COMMOM MANIFOLD
MUST BE SIZED TO
ACCOMMODATE COMBINED
FLOW RATE FOR
ALL BOILERS

Figure 4-8_Primary/secondary piping with buffer tank

*Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.

NOTICE

Installation & Service Manual

4

Water connections

COMMON MANIFOLD SIZE (Min.)

Models: 497 - 747

Number of Units

GPM

Diameter

(in.)

2

120

3 1/2

3

180

4

4

240

5

5

300

5

6

360

6

7

420

6

8

480

6

COMMON MANIFOLD SIZE (Min.)

Models: 987 - 2067

Number of Units

GPM

Diameter

(in.)

2

180

4

3

270

5

4

360

6

5

450

6

6

540

6

7

630

8

8

720

8