General information
You must supply adequate combustion and ventilation air to this unit. You must provide minimum clearances for the vent
terminal from adjacent buildings, windows that open, and building openings. Follow all requirements set forth in the latest edition
of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CAN/CGA Standard B149 Installation Code for Gas
Burning Appliances and Equipment or applicable local building codes. Vent installations for connection to gas vents or chimneys
must be in accordance with Part 7, “Venting of Equipment” of the above-mentioned standards.
NOTICE
Examine the venting system at least once each year. Check all joints and vent pipe connections for tightness. Also
check for corrosion or deterioration. If you find any problems, correct them at once.
Venting support
Support horizontal portions of the venting system to prevent sagging. Provide an upward slope of at least 1/4 inch per foot
(21mm/m) on all horizontal runs from the unit to the vertical flue run or to the vent terminal on sidewall venting installations.
Do not use an existing chimney as a raceway if another appliance or fireplace is vented through the chimney. The weight of the
venting system must not rest on the unit. Provide adequate support of the venting system. Follow all local and applicable codes.
Secure and seal all vent connections. Follow the installation instructions from the vent material manufacturer.
Vertical vent termination clearances and location
The vent terminal should be vertical and exhaust outside the building at least 2 feet (0.61m) above the highest point of the roof
within a 10 foot (3.05m) radius of the termination.
The vertical termination must be a minimum of 3 feet (0.91m) above the point of exit.
A vertical termination less than 10 feet (3.05m) from a parapet wall must be a minimum of 2 feet (0.61m) higher than the parapet
wall.
You must locate the air inlet termination elbow at least 12'' (30cm) above the roof or above normal snow levels.
Keep the vent cap clear of snow, ice, leaves, and debris to avoid blocking the flue.
2
Venting
16
Figure 2-1_Vent termination from peaked roof - 10 ft. or
less from ridge
NOTICE
Vent terminations are not shown in FIG.’s 2-1 thru 2-4. Make sure all vertical vents are installed with vent
terminations recommended by the vent manufacturer.
Figure 2-2_Vent termination from peaked roof - 10 ft. or
more from ridge
ƽ
DANGER
Failure to use correct venting materials can result in loss of life from flue gas spillage into working or living
space.
Installation & Service Manual