Gas connections

24

Combination gas valves

These units fire in multiple stages of burner input. Each stage
of burner operation has a combination gas valve(s) to cycle
the gas supply on and off and regulate gas to the burners. Each
combination valve consists of a gas regulator and two valve seats
to meet the requirements for redundant gas valves. The valve
has a gas control knob that must remain in the open position
at all times when the unit is in service. The gas control valve
has pressure taps located on the inlet and discharge sides of the
valve. Manifold pressure is adjusted using the regulator located
on the valve. A manifold gas pressure tap for each burner stick
is located on the discharge side of the valve. The manifold
pressure is preset at the factory and adjustment is not usually
required. If you must adjust regulator pressure, follow the
instructions under Gas Manifold Pressure Adjustment, page 25.

Venting of combination gas valves

The combination gas valve/regulator used on all units is
equipped with an integral vent limiting orifice per ANSI Z21.78.
The vent limiter ensures that the volume of gas emitted from
the valve in the event of a failed gas diaphragm does not exceed
the maximum safe leakage rate allowed by agency requirements.

Combination gas valve/regulators equipped with integral vent
limiters are not required to have vent or relief lines piped to
the outdoors. The termination of the vent limited opening on
the combination gas valve/regulator complies with the safety
code requirements of CSD-1, CF-190(a) as shipped from the
appliance manufacturer without the installation of additional
vent lines.

Checking gas supply pressure

Use the following procedure to check gas supply pressure.

1. Turn the main power switch to the “OFF” position.

2. Turn gas valve knobs to the “OFF” position.

3. Shut off gas supply at the field-installed manual gas cock in

the gas piping to the unit. If fuel supply is L.P. gas, shut off
gas supply at the tank.

4. Remove the 1/8'' hex plug, located on the “inlet” side of the

gas valve (FIG. 3-3). You may also use a tapping on the
field-installed main manual gas cock or gas piping. Install a
fitting in the inlet pressure tapping suitable to connect to a
manometer or magnehelic gauge. Range of scale should be
14'' w.c. or greater to check inlet pressure.

5. Turn on gas supply at the manual gas cock, turn on L.P. gas

at the tank if required.

6. Turn the power switch to the “ON” position.

7. Turn the gas valve knobs to the “ON” position. Set the

electronic temperature control or thermostat to call for
heat.

8. Observe the gas supply pressure as all burners are firing.

Ensure that inlet pressure is within the specified range.
See Connecting To Gas Supply, page 22 for minimum and
maximum gas supply pressures.

9. If gas pressure is out of range, contact gas utility, gas

supplier, qualified installer or service agency to determine
necessary steps to provide proper gas pressure to the
control.

TABLE 3D

GAS PIPING SIZE CHART

Nominal

Iron Pipe

Size

Inches

Length of Pipe in Straight Feet

Maximum

Capacity of Pipe
in Thousands of

Btu/hr per hour

for gas pressures

of 14 Inches

Water Column

(0.5 PSIG) or less

and a pressure

drop of 0.5 Inch

Water Column

(Based on NAT

GAS, 1025 Btu/hr

per Cubic Foot

of Gas and 0.60

Specific Gravity)

10

20

30

40

50

60

70

80

90

100

125

150

175

200

3/4

369

256

205

174

155

141

128

121

113

106

95

86

79

74

1

697

477

384

328

292

267

246

256

210

200

179

164

149

138

1 1/4

1,400

974

789

677

595

543

502

472

441

410

369

333

308

287

1 1/2

2,150

1,500

1,210

1,020

923

830

769

707

666

636

564

513

472

441

2

4,100

2,820

2,260

1,950

1,720

1,560 1,440 1,330

1,250

1,180

1,100

974

871

820

2 1/2

6,460

4,460

3,610

3,100

2,720

2,460 2,310 2,100

2,000

1,900

1,700 1,540 1,400

1,300

3

11,200

7,900

6,400

5,400

4,870

4,410 4,000 3,800

3,540

3,300

3,000 2,720 2,500

2,340

4

23,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690

7,380

6,870

6,150 5,640 5,130

4,720

Installation & Service Manual