Service procedures – Sanyo CL4232 User Manual
Page 55

– 55 –
SM830078
12. SERVICE PROCEDURES
3)
Outdoor Unit does not Run.
A. Check COOL / FAN selector switch in the remote control unit.
B. Check set temperature.
0624_X_S
Try to lower set
temperature by Temperature
setting button “COOLER”.
• Set “Operation selector”
switch to TEST in the
indoor unit.
YES
Outdoor unit runs.
Is room temperature too
low ?
NO
• Try to run both indoor and
outdoor units with another
remote control unit.
OK
The other remote control
unit is defective.
(Room sensor in the remote
control unit is defective.)
0623_X_S
• Is COOL/FAN selector switch
set to COOL ?
NO
Set to COOL.
This manual is related to the following products:
See also other documents in the category Sanyo Conditioners:
- ECO-i WCHDZ20053 (2 pages)
- CL0951 (3 pages)
- ECO G SPW-GU075XH (9 pages)
- CM1972 (99 pages)
- CR365GX56 (1 page)
- 42XS32A (3 pages)
- CL2432A (3 pages)
- 9 (2 pages)
- KH3072R / C3072R (180 pages)
- CH0971 (2 pages)
- 26UW72R (2 pages)
- C2432 (17 pages)
- CR1304GDZH8 (1 page)
- KH2672R (48 pages)
- ECOi C0905DXHN8 (10 pages)
- CH1251 (98 pages)
- 30KS32A (3 pages)
- Concealed Duct & Heat Pump H 13.9-14.9 SEER (2 pages)
- 42TLS32A (3 pages)
- CL2462R (58 pages)
- C1251 (83 pages)
- DHX3652 (114 pages)
- 42XHW72R (2 pages)
- 09KS71 (2 pages)
- C3632A (3 pages)
- 18KS72 (2 pages)
- 12XS71 (2 pages)
- ECO R410A (48 pages)
- KS2472 (117 pages)
- INVERTER SPLIT SYSTEM 8.53E+13 (24 pages)
- C3082 (104 pages)
- KHHS2672R (4 pages)
- CHX06052 (246 pages)
- CL1211 (16 pages)
- CH3082 (109 pages)
- Indoor Unit thx1852 (4 pages)
- 42TW72R (2 pages)
- KHS1872 (111 pages)
- CHDZ14053 (265 pages)
- CL0971 (4 pages)
- CHDX14053 (243 pages)
- 09KS51 (3 pages)
- 12RLS11 (3 pages)
- CL1852 (81 pages)