– 52 –

SM830078

12. SERVICE PROCEDURES

(b) Circuit breaker trips in several minutes after turning the air conditioner on.

• There is a possibility of short circuit.

2

2

2

2

2

Neither indoor unit nor outdoor unit runs.

A. Power is not supplied

B. Check remote control unit.

0615_X_S

• Check power supply.
Is power being supplied
to outdoor unit ?

Circuit breaker
is tripped.

Power failure.

Reset the breaker.

Wait for recovery
or consult power
supply company.

NO

• Check capacity of circuit
breaker.

NO

• Check resistance of
outdoor fan motor winding.

0614_X_S

Is capacity of circuit
breaker sufficient ?

• Check resistance of
compressor motor winding.

Replace it with a
suitable one.
(= larger capacity)

0616_X_S

• Try to run both indoor and
outdoor units with another
remote control unit.

Refer to item C.

NO

The other remote control
unit is defective.

OK