beautypg.com

Service procedures – Sanyo CL4232 User Manual

Page 51

background image

– 51 –

SM830078

12. SERVICE PROCEDURES

2)

Air Conditioner does not Operate

1

1

1

1

1

Circuit breaker trips (or fuse blows).

(a) When the circuit breaker is set to ON, it is tripped soon.

• There is a possibility of ground fault.
• Check insulation resistance.

If resistance value is 1 M

or less, it is a defect of insulation.

1

2

3

(Example)

*Set the circuit breaker to OFF.

Remove power supply cords
from the terminal plate in
the outdoor unit.
• Check insulation resistance
of power supply cords.

OK

NO

NO

Insulation of
outdoor unit
is defective.

Execute

rewiring.

Remove inter-unit power line
from the terminal plate in
the outdoor unit.
• Check insulation resistance
of outdoor unit.

OK

Remove inter-unit power line
from the terminal plate in
the indoor unit.
• Check insulation resistance
of indoor unit.

OK

Inter-unit power lines are
defective.

NO

Insulation of
indoor unit
is defective.

• Check insulation
resistance of
electrical parts
in the outdoor unit.

• Check insulation
resistance of
electrical parts
in the indoor unit.

Execute

rewiring.

1340_X_S

+
+

+

+

+

+

1

3

2

Circuit
breaker

Power
supply
cords

Inter-unit
power line

Outdoor

unit

Indoor

unit

Ground

+

+

4

1
2

G

L1
L2

G

4

1
2

G

4

This manual is related to the following products: