Preparation (Step 1 Connection/Installation)

Connect the alarm input/output terminals to
external devices such as sensors and buzzers.

1

Loosen the screws on both edges of the
terminal block using a flathead screwdriver,
followed by dismantling it as shown in the left
diagram.

2

Strip the coating of the alarm signal cable by
about 4mm (1/8 inches) before inserting it into
the terminal.

3

Turn the screw on the side to fasten the alarm
signal cable.

* Connect the alarm terminal according to

step 4 of “2 Installation.” (

Page 20)

1-2 Mounting the Camera to the Ceiling (Continued)

Connect this terminal to an infrared, door or
metallic sensor, or to a manual switch.

Input Requirements
● No-voltage relay or NPN open collector input

● The polarity of input detection can be selected

via software

● Make/Break/Toggle (at least 250 ms)

● Circuit current at low-level: 1.2 mA

● Voltage applied at high level: 12 V

Alarm Input Terminal

OUT

R

DC12V

GND

1.2mA

R

VCC

OUT

GND

12V

VN-C205

(Alarm Input
Equivalent Circuit)

Grounding
Terminal

Sensor
Connection
Example (1)

Relay, switch,
etc.

Sensor
Connection
Example (2)

Note

Cable Specifications

50 m or shorter in length

UL1007, UL1015 or equivalent

AWG#22 to AWG#18 or equivalent

Caution

Due to external noise, the cable may not
function properly even when the cable length
is less than 50 m. In this case, use a shielded
cable or take measures such as keeping the
cable away from the noise source.

Alarm Signal
Cable

Flathead
Screwdriver

Flathead
Screwdriver

4 mm (1/8 inches)

1

2

3

1

Connection to Alarm Input/Output Terminal

1. Preparations (Continued)