Error code
(SD0)
Error contents and cause
Corrective action
1000
1001
1002
1003
1004
1005
1006
1007
1008
1009
Runaway or failure of CPU module.
(1) Malfunctioning due to noise or other reason
(2) Hardware fault
1105
The CPU shared memory in the CPU module is faulty.
1150
The memory of the CPU module in the Multiple CPU high speed
transmission area is faulty.
(1) Take noise reduction measures.
(2) Reset the CPU module and RUN it again. If the same error is
displayed again, this suggests a CPU module hardware fault.
Explain the error symptom and get advice from our sales
representative.
1300
There is an output module with a blown fuse.
Check FUSE. LED of the output modules and replace the module whose
LED is lit.
1401
There was no response from the Motion module/intelligent function
module in the initial processing.
Set the Motion module/intelligent function module used in the Motion CPU
in the system setting.
This suggests a Motion module, intelligent function module, CPU module
and/or base unit is expecting a hardware fault.
Explain the error symptom and get advice from our sales representative.
1403
(1) An error is detected at the intelligent function module.
(2) The I/O module (including intelligent function module) is nearly
removed or completely removed/mounted during running.
The CPU module, base unit and/or the intelligent function module that
was accessed is experiencing a hardware fault.
Explain the error symptom and get advice from our sales representative.
1413
1414
An error is detected on the system bus.
1415
Fault of the main or extension base unit was detected.
1416
System bus fault was detected at power-on or reset.
Reset the CPU module and RUN it again. If the same error is displayed
again, the intelligent function module, CPU module or base unit is faulty.
Explain the error symptom and get advice from our sales representative.