Required schema file '' not found, Runtime project update failed, Starting opc diagnostics – IDEC WindSRV User Manual
Page 149: Stopping opc diagnostics
148
www.kepware.com
KEPServerEX5 Help
The specified project was opened.
Solution:
N/A.
Required schema file '
Error Type:
Error
Source:
Configuration
Possible Cause:
A project formatted with XML was loaded but the specified schema file was not found in the schemas folder.
Solution:
Re-run the server install and make sure that all the drivers are updated. This will re-install any missing schema files.
Runtime project update failed
Error Type:
Error
Source:
Configuration
Possible Cause:
The client attempted to update the Runtime project and failed.
Solution:
1. The user may not have permission to make changes to the project. Log in to the User Manager with the correct user
credentials.
2. The project folder may be locked to changes. Verify that all users with access to the project have permissions in the
folder.
Starting OPC diagnostics
Error Type:
Information
Source:
Configuration
Possible Cause:
OPC diagnostics captures were started by a connected Configuration.
Solution:
N/A.
Stopping OPC diagnostics
Error Type:
Information
Source:
Configuration