13al, 13bn – IDEC WindSRV User Manual
Page 114
![background image](/manuals/350373/114/background.png)
113
www.kepware.com
KEPServerEX5 Help
most significant bits are ignored.
Read Algorithm
Reads from a 16-bit register using the following algorithm:
Result =((Raw_value/4095) * Span_egu) + Lo_egu.
Read Algorithm Variables
Lo_egu - the database block's low engineering value.
Span_egu - the span of the engineering values.
Raw_value - the value stored in the field device's register.
Result - the scaled value stored in the database block.
Write Algorithm
Writes to a 16-bit register using the following algorithm:
Result =(((InputData - Lo_egu)/Span_egu) * 4095) + .5.
Write Algorithm Variables
Lo_egu - the low engineering value.
Span_egu - the span of the engineering values.
InputData - the database block's current value.
Result - the value sent to the process hardware.
13AL Signal Conditioning
Description
13-bit binary number.
Input Range
0 - 8191.
Scaling
Scales 13-bit binary values to the database block's EGU range.
Read Algorithm
Reads from a 16-bit register using the same algorithm as 13BN, and
returns a status indicating whether the value is out of range and in an
alarm state, or OK.
Result=((Raw_value/8191) * Span_egu) + Lo_egu.
Read Algorithm Variables
Lo_egu - the database block's low engineering value.
Span_egu - the span of the engineering values.
Raw_value - the value stored in the field device's register.
Result - the scaled value stored in the database block.
Write Algorithm
Writes to a 16-bit register using the same algorithm as 13BN, and
returns a status indicating whether the value is out of range and in an
alarm state, or OK.
Result=(((InputData - Lo_egu)/Span_egu) * 8191) + .5.
Write Algorithm Variables
Lo_egu - the low engineering value.
Span_egu - the span of the engineering values.
InputData - the database block's current value.
Result - the value sent to the process hardware.
13BN Signal Conditioning
Description
13-bit binary number.
Input Range
0 - 8191.
Scaling
Scales 13-bit binary values to the database block's EGU range. Ignores
the most significant 3 bits.
Read Algorithm
Reads from a 16-bit register using the following algorithm:
Result =((Raw_value/8191) * Span_egu) + Lo_egu.
Read Algorithm Variables
Lo_egu - the database block's low engineering value.
Span_egu - the span of the engineering values.
Raw_value - the value stored in the field device's register.
Result - the scaled value stored in the database block.
Write Algorithm
Writes to a 16-bit register using the following algorithm:
Result =(((InputData - Lo_egu)/Span_egu) * 8191) + .5.
Write Algorithm Variables
Lo_egu - the low engineering value.
Span_egu - the span of the engineering values.
InputData - the database block's current value.
Result - the value sent to the process hardware.