14al, 14bn, 15al – IDEC WindSRV User Manual
Page 115
114
www.kepware.com
KEPServerEX5 Help
14AL Signal Conditioning
Description
14-bit binary number.
Input Range
0 - 16383.
Scaling
Scales 14-bit binary values to the database block's EGU range.
Read Algorithm
Reads from a 16-bit register using the same algorithm as 14BN, and
returns a status indicating whether the value is out of range and in an
alarm state, or OK.
Result=((Raw_value/16383) * Span_egu) + Lo_egu.
Read Algorithm Variables
Lo_egu - the database block's low engineering value.
Span_egu - the span of the engineering values.
Raw_value - the value stored in the field device's register.
Result - the scaled value stored in the database block.
Write Algorithm
Writes to a 16-bit register using the same algorithm as 14BN, and
returns a status indicating whether the value is out of range and in an
alarm state, or OK.
Result=(((InputData - Lo_egu)/Span_egu) * 16383) + .5.
Write Algorithm Variables
Lo_egu - the low engineering value.
Span_egu - the span of the engineering values.
InputData - the database block's current value.
Result - the value sent to the process hardware.
14BN Signal Conditioning
Description
14-bit binary number.
Input Range
0 - 16383.
Scaling
Scales 14-bit binary values to the database block's EGU range. Ignores
the most significant 2 bits.
Read Algorithm
Reads from a 16-bit register using the following algorithm:
Result=((Raw_value/16383) * Span_egu) + Lo_egu.
Read Algorithm Variables
Lo_egu - the database block's low engineering value.
Span_egu - the span of the engineering values.
Raw_value - the value stored in the field device's register.
Result - the scaled value stored in the database block.
Write Algorithm
Writes to a 16-bit register using the following algorithm:
Result=(((InputData - Lo_egu)/Span_egu) * 16383) + .5.
Write Algorithm Variables
Lo_egu - the low engineering value.
Span_egu - the span of the engineering values.
InputData - the database block's current value.
Result - the value sent to the process hardware.
15AL Signal Conditioning
Description
15-bit binary number.
Input Range
0 - 32767.
Scaling
Scales 15-bit binary values to the database block's EGU range.
Read Algorithm
Reads from a 16-bit register with alarming using the same algorithm
as 15BN, and returns a status indicating whether the value is out of
range and in an alarm state, or OK.
Result=((Raw_value/32767) * Span_egu) + Lo_egu.
Read Algorithm Variables
Lo_egu - the database block's low engineering value.
Span_egu - the span of the engineering values.
Raw_value - the value stored in the field device's register.
Result - the scaled value stored in the database block.