beautypg.com

Getting started, A. design, installation & location considerations, B. fire safety – Harman Stove Company P35I User Manual

Page 6: Caution warning

background image

6

P35i Fireplace Insert

Pellets or Corn/Pellet Mixture Only

Save These Instructions

3-90-775R15_04/13

3

Getting Started

A. Design, Installation & Location

Considerations

1. Appliance Location
Consideration must be given to safety, convenience, traffic

flow, and the fact that the appliance will need to be vented

to the outside.

This appliance may only be installed into

an existing masonry or manufactured wood-burning

fireplace or using the optional zero-clearance cabinet to

build into a newly constructed chase. It is a good idea to

plan your installation on paper. Use exact measurements for

clearances and floor protection, before actually beginning

the installation.
Maintain specified vent clearance to combustible

requirements listed by the vent manufacturers instructions

and all appliance clearances as listed in this manual.
Check with your local building code agency before you

begin your installation. Local codes may supersede the

test laboratories specifications. Always obtain any required

permit(s) so that insurance protection benefits cannot be

unexpectedly cancelled. If any assistance is required during

installation, please contact your dealer.
We recommend that a qualified building inspector and your

insurance company representative review your plans before

and after the installation.
2. Room Sensor Location
The room sensor's location will have some effect on the

appliance's operation. When the sensor is located close to

the appliance, it may require a higher setting to keep the

rest of the house comfortable. If the sensor is located in

an adjacent room, or farther away from the stove, you will

notice higher temperatures near the appliance.

Do NOT connect this unit to a chimney flue

servicing another appliance.

• Do NOT connect to any forced air distribution duct

or system.

B. Fire Safety

Maintain the designated clearances to combustibles.

Insulation must not touch the chimney. You must maintain

the designated air space around the chimney. This space

around a chimney is necessary to allow natural heat

removal from the area. Insulation in this space will cause

a heat buildup, which may ignite wood framing.

NOTE:

Clearances may only be reduced by means approved

by the regulatory authority having jurisdiction.
To provide reasonable fire safety, the following should be

given serious consideration:
1. Install at least one smoke detector on each floor of

your home. Detectors should be located away from

the heating appliance and close to sleeping areas.

Follow the smoke detector manufacturer's placement

and installation instructions, and be sure to maintain

regularly.

2. A conveniently located Class A fire extinguisher to

contend with small fires resulting from burning embers.

3. A practiced evacuation plan, consisting of at least two

escape routes.

4. A plan to deal with a hopper fire as follows:
In the event of a hopper fire:
a. Turn appliance to "OFF".
b.

Be sure hopper lid is closed and latched.

c. Notify Fire Department.
d. Do NOT pour water in the hopper.
e.

Never pull the plug or otherwise disconnect the

power supply to kill a fire.

Fire Hazard

• Do not operate appliance before

reading and understanding the

operating instructions.

• Failure to operate properly may

cause a house fire.

CAUTION

WARNING