beautypg.com

B. avoiding smoke and odors – Harman Stove Company P35I User Manual

Page 13

background image

13

Pellets or Corn/Pellet Mixture Only

P35i Fireplace Insert

Save These Instructions

3-90-775R15_04/13

NOTE: The restriction of not venting more than

one appliance to the same flue applies to the U.S.

specifically. While it is not recommended that you use

the same chimney for more than one appliance, in

Canada certain exceptions may be made. Be sure to

contact your building code inspection official to see if

this option is allowed in your area, and to find out the

specific requirements for such an installation.

Do not connect this unit to a chimney flue

servicing another appliance.

B. Avoiding Smoke and Odors

Negative Pressure, Shut-down, and Power

Failure:

T

o reduce the probability of back-drafting or burn-

back in the pellet burning appliance during power

failure or shut-down conditions, the stove must

be able to draft naturally without exhaust blower

operation. Negative pressure in the house will resist this

natural draft if not accounted for in the pellet appliance

installation.
Heat rises in the house and leaks out at upper levels.

This air must be replaced with cold air from outdoors,

which flows into lower levels of the house. Vents and

chimneys into basements and lower levels of the house

can become the conduit for air supply, and reverse

under these conditions.

Outside Air:

Hearth & Home Technologies recommend attaching

outside air in all installations, especially lower level

and main floor locations.
Per national building codes, consideration must be given

to combustion air supply to all combustion appliances.

Failure to supply adequate combustion air for all

appliance demands, may lead to back-drafting of those

and other appliances.
When the appliance is side-wall vented: The air intake

is best located on the same exterior wall as the exhaust

vent outlet and located lower on the wall than the

exhaust vent outlet.
When the appliance is roof vented: The air intake is

best located on the exterior wall oriented towards the

prevailing wind direction during the heating season.
The outside air connection will supply the demands of

the pellet appliance, but consideration must be given to

the total house demand. House demand may consume

some air needed for the stove, especially during a power

failure. It may be necessary to add additional ventilation

to the space in which the pellet appliance is located.

Consult with your local HVAC professional to determine

the ventilation demands for your house.
The outside air kit consists of a flue stub pipe, fiberglass

gasket, silicone gasket, intake box and a section of flex

pipe.
An adjustable chimney intake extension, part # 1-00-

674104 is available to be used on masonry chimneys

only.
To install outside air, use kit part number 1-00-774280.

Follow the installation instructions provided with the kit.

Vent Configurations:

To reduce probability of reverse drafting during shut-

down conditions, Hearth & Home Technologies strongly

recommends:
• Installing the pellet vent with a minimum vertical run

of five feet, preferably terminating above the roof line.

• Installing the outside air intake at least four feet below

the vent termination.

To prevent soot damage to exterior walls of the house

and to prevent re-entry of soot or ash into the house:
• Maintain specified clearances to windows, doors,

and air inlets, including air conditioners.

• Vents should not be placed below ventilated soffits.

Run the vent above the roof.

• Avoid venting into alcove locations.
• Vents should not terminate under overhangs, decks

or onto covered porches.

• Maintain minimum clearance of 12 inches from

the vent termination to the exterior wall. If you see

deposits developing on the wall, you may need

to extend this distance to accommodate your

installation conditions.

Hearth & Home Technologies assumes no

responsibility for, nor does the warranty extend

to, smoke damage caused by reverse drafting of

pellet appliances under shut-down or power failure

conditions.

Do not connect this unit to any air distribution

duct or system.