beautypg.com

Removing the hex coupling – HP 403349-003 User Manual

Page 78

background image

Removal and replacement procedures 78

Removing the HEX coupling

1.

Shut off the water flowing into the MCS unit. ("

Shutting off the water

" on page

25

)

2.

Remove the corresponding fan unit. ("

Removing the fan unit

" on page

51

)

3.

Remove the corresponding air deflector plate. ("

Removing the air deflector plate

" on page

33

)

4.

Disconnect the temperature sensor cable from the heat exchanger unit.

5.

Slide back the insulation on either the In or Out water hose.

6.

Using the water hose fitting wrench and the counter hold wrench, disconnect either the In or Out
water hose from the heat exchanger unit.