beautypg.com

Heat exchanger unit (hex) with ball valve – HP 403349-003 User Manual

Page 67

background image

Removal and replacement procedures 67

6.

Using the counter hold wrench to hold the fitting in place and the water hose fitting wrench to tighten

the water hose (both wrenches are included with your original MCS unit), connect the In and Out
water hoses to the heat exchanger unit.

7.

Connect the temperature sensor connector to the heat exchanger unit.

8.

Replace the air deflector plate ("

Replacing the air deflector plate

" on page

34

).

9.

Replace the fan unit ("

Replacing the fan unit

" on page

52

).

Complete the operation checklist (on page

111

).

Heat exchanger unit (HEX) with ball valve

The three heat exchanger units are located on the front of the MCS unit.