Removal and replacement procedures 107
Water temperature sensor
The water temperature sensor is a component of the water group located at the bottom interior of the
MCS unit.
The following tools are required for installation:
•
T-25 Torx driver
•
Phillips screwdriver
•
(2) 18-mm wrench
•
Wire cutters
Removing the water temperature sensor
1.
Power down the MCS unit. ("
2.
Shut off the water flowing into the MCS unit. ("
3.
Remove the bottom fan unit. ("
4.
Relocate the power inlet box. ("
Relocating the power inlet box
5.
Remove the air sealing plate. ("
Removing the air sealing plate
6.
Remove the air deflector plate. ("
Removing the air deflector plate
7.
Remove the condensation pump and sensors. ("
Removing the condensation pump and sensors
8.
Remove the AC transfer switch. ("
Removing the AC transfer switch
NOTE:
HP recommends removing the In and Out water hoses and all cables to the bottom
heat exchanger unit in order to gain greater access.