ProSoft Technology 5204-DFNT-PDPMV1 User Manual
Page 93
DFNT ♦ ProLinx Gateway
Reference
EtherNet/IP Explicit Messaging Client/Server
Protocol Manual
ProSoft Technology, Inc.
Page 93 of 124
July 24, 2013
5.7.1 DDE Connection
This section discusses setting up a DDE connection to the module in order to
transfer data between the module and a DDE compliant application.
Each DDE connection requires three basic elements: Application, Topic and
Item. These three properties of a DDE link define the program providing the
connection, the topic to connect to and the item in the topic that you wish to
interface. All three are required for a connection. For this discussion, the
Application will always be RSLinx. The Topic is defined in the RSLinx OEM
release software and the Item is defined in the DDE client application where the
data is required. The link between the DDE server and the DDE client can be
established after these parameters are defined. The following illustration shows
the relationship of these elements and the facilities used in the DDE link.
1 The DDE Client application specifies the DDE link by specifying the
APPLICATION, TOPIC, and ITEM elements. For example, in Excel, enter
=RSLINX|CIP_Sample! 'ReadData[0]' into a cell.
2 RSLinx is the DDE Server: APPLICATION = RSLINX.
And
RSLinx defines the TOPIC.
This is the communication link to the DFNT module. In this example, a DDE
TOPIC is called "CIP_Sample" for the communication link to the DFNT
module.
3 The DFNT module is used to serve data to RSLinx using the EtherNet/IP
driver with explicit messaging. Database is accessed using tag names (e.g.
ReadData[0]).
- 5205-DFNT-PDPS 5202-DFNT-MCM4 5201-DFNT-MCM 5201-DFNT-104S 5207-DFNT-HART 5228-DFNT-HART 5208-DFNT-HART 5201-DFNT-EGD 5202-DFNT-GRCM4 5201-DFNT-GRCM 5201-DFNT-DNPS 5201-DFNT-DNPSNET 5201-DFNT-DNPM 5201-DFNT-DH485 5202-DFNT-DFCM4 5201-DFNT-DFCM 5201-DFNT-BACNET 5201-DFNT-ASCII 5210-DFNT-RIO 5303-MBP-DFNT 5201-MNET-DFNT 5201-DFNT-104C