ProSoft Technology 5204-DFNT-PDPMV1 User Manual
Page 107
DFNT ♦ ProLinx Gateway
Reference
EtherNet/IP Explicit Messaging Client/Server
Protocol Manual
ProSoft Technology, Inc.
Page 107 of 124
July 24, 2013
5.9.2 CIP Data Table Operations
This method of data transfer uses CIP messages to transfer data between the
ControlLogix processor and the module. Tag names define the elements to be
transferred. The following topics describe the support for the read and write
operations.
CIP Data Table Write
CIP data table write messages transfer data from the ControlLogix processor to
the DFNT module. An example rung used to execute a write command is shown
in the following diagram:
The M
ESSAGE
C
ONFIGURATION
dialog box must be completed to define the data
set to be transferred from the processor to the module. An example of the dialog
box follows:
Complete the dialog box for the data area to be transferred. CIP Data Table
messages require a tag database element for both the source and destination.
The S
OURCE
T
AG
is a tag defined in the ControlLogix Tag database. The
D
ESTINATION
E
LEMENT
is the tag element in the DFNT module.
The module simulates a tag database as an array of elements defined by the
maximum register size for the module (user configuration parameter "Maximum
Register" in the [Module] section) with the tag name
INT
_
DATA
.
- 5205-DFNT-PDPS 5202-DFNT-MCM4 5201-DFNT-MCM 5201-DFNT-104S 5207-DFNT-HART 5228-DFNT-HART 5208-DFNT-HART 5201-DFNT-EGD 5202-DFNT-GRCM4 5201-DFNT-GRCM 5201-DFNT-DNPS 5201-DFNT-DNPSNET 5201-DFNT-DNPM 5201-DFNT-DH485 5202-DFNT-DFCM4 5201-DFNT-DFCM 5201-DFNT-BACNET 5201-DFNT-ASCII 5210-DFNT-RIO 5303-MBP-DFNT 5201-MNET-DFNT 5201-DFNT-104C