ProSoft Technology 5204-DFNT-PDPMV1 User Manual

Page 81

background image

DFNT ♦ ProLinx Gateway

Reference

EtherNet/IP Explicit Messaging Client/Server

Protocol Manual

ProSoft Technology, Inc.

Page 81 of 124

July 24, 2013

5.2.13 Function Code #502 - Protected Typed Logical Read (Three

Address Fields)

Column

Parameter

Description

Parameter

1

Enable/Type Word

0=Disabled and 1=Continuous.

2

Virtual Database Address

This parameter defines the database address of the first

data point to be associated with the command.

3

Poll Interval

Minimum number of seconds to wait before polling with
this command.

4

Count

Number of data word values to be considered by the
function.

5

Swap Type Code

Swap type code for command: 0=None, 1=Swap words,

2=Swap words & bytes and 3=swap bytes in each word.

6

Node Address

Address of unit to reach on the data highway.

7

Slot Number

Processor slot number in Control/CompactLogix rack.

Use -1 for PLC5 & SLC processors.

8

Function Code = 502

Logical Read Command

9

File Type

SLC file type letter as used in file name string. Valid
values for the system are N, S, F, A, ….

P1

10

File Number

SLC file number to be associated with the command.

P2

11

Element Number

The parameter defines the element in the file where
write operation will start.

P3

12

Sub-Element Number

This parameter defines the sub-element for the
command. Refer to the AB documentation for a list of

valid sub-element codes.

P4

This function reads one or more words of data from a PLC data table. This
function should work on the following devices: SLC 500, SLC 5/03 and SLC 5/04.