beautypg.com

ProSoft Technology 5204-DFNT-PDPMV1 User Manual

Page 46

background image

Configuring the Gateway

DFNT ♦ ProLinx Gateway

Protocol Manual

EtherNet/IP Explicit Messaging Client/Server

Page 46 of 124

ProSoft Technology, Inc.

July 24, 2013

You may need to swap the order of the bytes in the registers during the copy
process in order to change the alignment of bytes between dissimilar protocols.
This parameter is helpful when dealing with floating-point or other multi-register
values, as there is no standard method of storage of these data types in slave
devices.

The following table defines the values and their associated operations:

Swap Code

Description

No Swap

No change is made in the byte ordering (1234 = 1234)

Word Swap

The words are swapped (1234=3412)

Word and
Byte Swap

The words are swapped, then the bytes in each word are swapped (1234=4321)

Bytes

The bytes in each word are swapped (1234=2143)