Controllogix (clx) processor – ProSoft Technology 5204-DFNT-PDPMV1 User Manual
Page 103
DFNT ♦ ProLinx Gateway
Reference
EtherNet/IP Explicit Messaging Client/Server
Protocol Manual
ProSoft Technology, Inc.
Page 103 of 124
July 24, 2013
5.9
ControlLogix (CLX) Processor
In order to exchange data between a ControlLogix processor and the module, the
MSG instruction is used. There are two basic methods of data transfer supported
by the module when using the MSG instruction: Encapsulated PCCC messages
and CIP Data Table messages. Either method can be used, and the selection is
left to the application developer.
5.9.1 Encapsulated PCCC Messages
PLC5 and SLC5/05 processors containing an Ethernet interface use the
encapsulated PCCC message method. The module simulates these devices and
accepts both read and write commands. The following topics describe the
support for the read and write operations.
Encapsulated PCCC Write Message
Write commands transfer data from the ControlLogix processor to the module.
The following encapsulated PCCC commands are supported from a ControlLogix
Processor:
PLC2 Unprotected Write
PLC5 Typed Write
PLC5 Word Range Write
PLC Typed Write
An example rung used to execute a write command is shown in the following
diagram:
The M
ESSAGE
C
ONFIGURATION
dialog box must be completed to define the data
set to be transferred from the processor to the module. An example of the dialog
box follows:
- 5205-DFNT-PDPS 5202-DFNT-MCM4 5201-DFNT-MCM 5201-DFNT-104S 5207-DFNT-HART 5228-DFNT-HART 5208-DFNT-HART 5201-DFNT-EGD 5202-DFNT-GRCM4 5201-DFNT-GRCM 5201-DFNT-DNPS 5201-DFNT-DNPSNET 5201-DFNT-DNPM 5201-DFNT-DH485 5202-DFNT-DFCM4 5201-DFNT-DFCM 5201-DFNT-BACNET 5201-DFNT-ASCII 5210-DFNT-RIO 5303-MBP-DFNT 5201-MNET-DFNT 5201-DFNT-104C