Parameter activation – ProSoft Technology PTQ-101M User Manual
Page 85

Module Configuration
PTQ-101M ♦ Quantum Platform
IEC 60870-5-101 Master Communication Module
ProSoft Technology, Inc.
Page 85 of 181
May 14, 2008
The Qualifier Parameter used with this command is determined by summing the
options from lists that follow:
Kind of parameter:
0=Not
used
1=Threshold
value
2=Smoothing factor (filter time constant)
3=Low limit for transmission of measured values
3=High limit for transmission of measured values
5 to 31 = Reserved by standard
32 to 63 = Reserved for special use (private range)
Local parameter change:
0=No
change
64=Change
Parameter in operation:
0=Operation
128=Not in operation
Parameter Activation
The format of this field for the Parameter Activation (113) is as follows:
Parameter Activation Command
Bit
0
to
7
8
9
to
15
Not Utilized
Activation Qualifier
Description
Parameter Qualifier
No database value used with the construction of this command.
The Qualifier Parameter used with the command is determined by summing the
options from the lists that follow:
Parameter Qualifier:
0=Not
used
1=Act/Deact of previously loaded parameters (point index = 0)
2=Act/Deact of the parameter of the point index specified
3=Act/Deact of persistent cyclic or periodic transmission of the addressed
object
4 to 127 = Reserved by standard
128 to 255 = Reserved for special use (private range)