Error codes, 2 error codes – ProSoft Technology PTQ-101M User Manual
Page 155

Reference PTQ-101M
♦ Quantum Platform
IEC 60870-5-101 Master Communication Module
ProSoft Technology, Inc.
Page 155 of 181
May 14, 2008
7.5.2 Error
Codes
The following table lists all potential errors that can be generated by the IEC
60870-5-101 master driver:
Error Description
51
Physical layer error - Error transmitting message
52
Physical layer error - Intercharacter timeout occurred before message fully received.
53
Physical layer error - Frame not entirely received before timeout condition.
54
Physical layer error - Invalid frame length.
101
Link layer error - Invalid checksum received
102
Link layer error - Address unknown to module
103
Link layer error - Link established
104
Link layer error - Link failed
105
Link layer error - Received primary
106
Link layer error - FCB error discard
107
Link layer error - FCB error repeat
108
Link layer error - Invalid start character received
109
Link layer error - Invalid second character received
110
Link layer error - Invalid ending character received
111
Link layer error - Length mismatch error
112
Link layer error - Illegal function
113
Link layer error - No confirmation received
114
Link layer error - No ACK received
115
Link layer error - Sequence unknown
116
Link layer error - Out of sequence
117
Link layer error - Remote close
118
Link layer error - Unexpected ACK
119
Link layer error - Request cancelled
201
Application layer error - Length mismatch
202
Application layer error - Address unknown
203
Application layer error - Response late
251
RBE error - Clock event buffer overflow
252
RBE error - Event buffer overflow
271
Data error - Address unknown
281
Control error - Illegal operation
282
Control error - Illegal value
283
Control error - Not selected
301
Initialization error - Database
302
Initialization error - Out of memory
401 Channel
open
error
501
Session error - Database
502
Session error - Configuration
601
No memory to receive message