Page 69: Write register start

Module Configuration
PTQ-101M ♦ Quantum Platform
IEC 60870-5-101 Master Communication Module
ProSoft Technology, Inc.
Page 69 of 181
May 14, 2008
The following example shows a sample [Backplane Configuration] section:
[Backplane Configuration]
Module Name: PTQ-101M SAMPLE TEST MODULE
#These values are required to define the data area to transfer between the
#module and the processor.
Read Register Start : 0 #Database start register to move to processor
Read Register Count : 50 #Number of words moved from module to
#processor
Write Register Start: 1000 #Database start register where data placed
#from processor
Write Register Count: 50 #Number of words moved from processor to
#module
#Used to define the area in the Processor for the module to interface with
3x Register Start: 1 #3x start register where data moved from
#module to processor (1-n)
4x Register Start: 1 #4x start register where data moved from
#processor to module (1-n)
Pass-Through Events : N #Pass event messages to processor
Modify each of the parameters based on the needs of your application.
Module Name
0 to 80 characters
This parameter assigns a name to the module that can be viewed using the
configuration/debug port. Use this parameter to identify the module and the
configuration file.
Read Register Start
Range 0 to 3999
This parameter specifies the starting register in the module where the data
transferred from the processor will be placed. Valid range for this parameter is 0
to 3999.
Read Register Count
Range 0 to 3999
This parameter specifies the number of registers to be transferred from the
module to the processor. Valid entry for this parameter is 0 to 3999.
Write Register Start
0 to 3999
The Write Register Start parameter assigns the starting address for data to
retrieve from the processor.