Type
Description
DB Index type
100
Group interrogation command
NA
101
Counter interrogation command
NA
102 Read
command
NA
103 Clock
Synchronization
NA
104
Test command (101 standard)
NA
105
Reset process command
NA
107
Test command (104 standard)
NA
110
Parameter, normalized measured value
Word address
111
Parameter, scaled measured value
Word address
112
Parameter, short float value
Double-word address
113
Parameter activation command
NA
242
BCD integrated setpoint command
3 word address
255
Send a class 2 poll
NA
Point Index
Point Index field specifies the address in the remote slave device of the point to
interact with.
Qualifier Parameter
The Qualifier Parameter field defined for a command is dependent on the data
type used in the command. In order to compute the qualifier for a command, add
all the values for the features to use with a command together to form a single
number. This number should be entered in the command record. Each data set is
discussed below:
Single Point, Double Point, and Regulating Setup
The format of the field for Single Point (45), Double Point (46), and Regulating
Step (47)
commands is as follows:
Single Point, Double Point and Regulating Step Point Commands
Bit
Single
Double
Step
0
Value
Control
Control
1
0
Value
Value
2
3
4
5
6
7
8
9
10
to
15
Select/Execute Code
Qualifier Code
Not Utilized
Deselect Code
Use Override Value