Read command, Clock synchronization, Test command – ProSoft Technology PTQ-101M User Manual
Page 83

Module Configuration
PTQ-101M ♦ Quantum Platform
IEC 60870-5-101 Master Communication Module
ProSoft Technology, Inc.
Page 83 of 181
May 14, 2008
Read Command
The format of this field for the Read (102) command is as follows:
Read Command
Bit
0
to
15
Description
Not Utilized
No database value is associated with the construction of this command and no
qualifier value is used in this release of the software.
Clock Synchronization
The format of this field for the Clock Synchronization (103) command is as
follows:
Clock Synchronization Command
Bit
0
1
0
to
15
Description
Not Utilized
Synchronization Mode
Qualifier
No database value is associated with the construction of this command.
The Qualifier Parameter for this command has one of the following values:
0=Clock synchronization with out delay utilized
1=Synchronize clock with delay set
2=Measure delay, load delay then synchronize clock
Test Command
The format of this field for the test command (104 and 107) is as follows:
Test Command (both 101 and 104 versions)
Bit
0
to
15
Description
Not Utilized
No database value is associated with the construction of this command and no
qualifier value is used in this release of the software.