Normalized, scaled, and short float, Bitstring for 32 bits – ProSoft Technology PTQ-101M User Manual
Page 80

PTQ-101M ♦ Quantum Platform
Module Configuration
IEC 60870-5-101 Master Communication Module
Page 80 of 181
ProSoft Technology, Inc.
May 14, 2008
Normalized, Scaled, and Short Float
The format of the field for Normalized (48), Scaled (49), and Short Float (50)
setpoint command is as follows:
Normalized, Scaled and Short Float Setpoint Commands
Bit
0
1
2
to
15
Description
Not Utilized
Select/Execute Code
Deselect Code
The value read from database for point specified is used with this qualifier to
build a command.
The Qualifier Parameter uses one of the following codes:
0=Direct execution without select
1=Select executed followed by execute
2=Deselect
command
Bitstring for 32 Bits
The format of the field for 32-Bitstring (51) setpoint command is as follows:
Bitstring of 32 Bit Command
Bit
0
to
15
Description
Not Utilized
The value read from database for point specified is used with this qualifier to
build a command.
The Qualifier Parameter is not currently used to construct commands.