Configuration data definition, Configuration, Data definition – ProSoft Technology PTQ-101M User Manual
Page 156: 6 configuration data definition

PTQ-101M ♦ Quantum Platform
Reference
IEC 60870-5-101 Master Communication Module
Page 156 of 181
ProSoft Technology, Inc.
May 14, 2008
Error Description
602
Session not reserved
603 Illegal
session
604
Session is reserved
605
Session is not available
701
No memory to transmit message
702
ASDU not supported
703 Duplicate
request
704 Illegal
sector
705
Control mode is illegal
801
Partial stop request
802
Stop request failed
901 Response
timeout
902
Negative COT in response
903
Session is offline
904
Session is disabled
905
Select confirmation received, waiting to execute
906
Execute confirmation has not be received
7.6
Configuration Data Definition
This section contains a listing of the parameters and their definitions for the PTQ-
101M module configuration file definition (IEC101M.CFG).
[Section]/Item Value
Range
Description
[Backplane Configuration]
Backplane transfer parameters
Module Name:
0 to 80
characters
This parameter assigns a name to the module that
can be viewed using the configuration/debug port.
Use this parameter to identify the module and the
configuration file.
4x Register Start:
1 to n
This parameter sets the first register in the
processor where the data transferred from the
processor to the module is present.
Write Register Start:
0 to 3999
This parameter specifies the starting register in
the module where the data transferred from the
processor will be placed. Valid range for this
parameter is 0 to 3999.
Write Register Count:
0 to 4000
This parameter specifies the number of registers
to transfer from the processor to the module. Valid
entry for this parameter is 0 to 4000.
3x Register Start:
1 to n
This parameter sets the first register in the
processor where the data transferred from the
module to the processor will be placed.
Read Register Start:
0 to 3999
This parameter specifies the starting register in
the module where data will be transferred from the
module to the processor. Valid range for this
parameter is 0 to 3999.