Enable code, Database index, Poll interval – ProSoft Technology PTQ-101M User Manual
Page 77: Session index, Sector index, Data type

Module Configuration
PTQ-101M ♦ Quantum Platform
IEC 60870-5-101 Master Communication Module
ProSoft Technology, Inc.
Page 77 of 181
May 14, 2008
Enable Code
0 = Disabled
1 = Enabled with Poll Interval (seconds) utilized
2 = Conditional (executed when point in database changes)
This field defines whether or not the command is to be executed and under what
conditions. If the parameter is set to 0, the command is disabled and will not be
executed in the normal polling sequence. The command can be executed under
the control of the PLC processor through the use of a Command Control block.
Setting the parameter to a value of 1 for the command causes the command to
be executed each scan of the command list if the Poll Interval Time is set to zero.
If the Poll Interval time is set, the command will be executed, when the interval
timer expires. If the parameter is set to 2, the command will execute only if the
internal data associated with the command changes. This value is valid only for
write commands.
Database Index
Database Index is the location in the module's database to use as the source for
the data in the command. The data type (page 77) field determines the meaning
of the index.
Poll Interval
This parameter specifies the minimum frequency at which the module should
execute the command. The value is entered in units of seconds. For example, to
execute a command every 10 seconds, enter a value of 10 in the field. A value of
0 for the parameter implies that the command should be executed every scan of
the list.
Session Index
Session Index represents the session index in the module to associate with the
command. This index is set when the session is read in from this file. The range
of values for this field is 0 to 31.
Sector Index
Sector Index represents the sector index for the specific session. The range of
values for this field is 0 to 4.
Data Type
Data type file represents the ASDU type as follows:
Type
Description
DB Index type
45
Single point command
Bit address
46
Double point command
Bit address
47
Regulating Step point command
Byte address
48
Setpoint, normalized point command
Word address
49
Setpoint, scaled point command
Word address
50
Setpoint, short float point command
Double-word address
51
Bitstring (32-bits) point command
Double-word address