ProSoft Technology PTQ-101M User Manual
Page 160

PTQ-101M ♦ Quantum Platform
Reference
IEC 60870-5-101 Master Communication Module
Page 160 of 181
ProSoft Technology, Inc.
May 14, 2008
[Section]/Item Value
Range
Description
Use Time Tag
Commands:
Yes or No
This parameter specifies if a time tag field is to be
included with commands. This is as specified in
the IEC-870-5-104 specification and should only
be utilized if the controlled device supports these
new data types. If the parameter is set to Yes, a
time tag will be added to all commands. If the
parameter is set to No, the normal IEC 60870-5-
101 data type messages will be utilized.
Online Time Sync:
Yes or No
This parameter specifies if the sector in the
controlled device will be sent a time
synchronization command when the unit is first
recognized as being online. This should only be
utilized for devices that do not send an EOI
message after initializing.
Online General Int:
Yes or No
This parameter specifies if the sector in the
controlled device will be sent a general
interrogation command when the unit is first
recognized as being online. This should only be
utilized for devices that do not send an EOI
message after initializing.
EOI Time Sync:
Yes or No
This parameter specifies if the sector in the
controlled device will be sent a time
synchronization command after this module
received an EOI message from the controlled unit.
EOI General Int:
Yes or No
This parameter specifies if the sector in the
controlled device will be sent a general
interrogation command after this module received
an EOI message from the controlled unit.
# Data Type Point # DB Address
# --------- ---------- ----------
START
END
[Section]/Item
Description
[IEC-101 MASTER COMMANDS]
This section contains the commands for the
module
# Enable Database Poll Session Sector Data Point Qualifier
# Code Index Interval Index Index Type Index Parameter
# ------ -------- -------- ------- ------ ---- ----- ---------
START
END