ProSoft Technology MVI56-PDPS User Manual
Page 67
Reference MVI56-PDPS
♦ ControlLogix Platform
Profibus DP Slave Communication Module
ProSoft Technology, Inc.
Page 67 of 88
April 22, 2008
0000 = 12 MBaud
0001 = 6 MBaud
0010 = 3 MBaud
0011 = 1.5 MBaud
0100 = 500 kBaud
0101 = 187.5 kBaud
0110 = 93.75 kBaud
0111 = 45.45 kBaud
1000 = 19.2 kBaud
1001 = 9.6 kBaud
Rest = Not possible
SPC3-Release:
Release no. for SPC3
Bits
4 to 7
0000 = Release 0
Rest = Not possible
Diagnostic state - Word 211
0 = Normal Operation or not in data exchange with Status Register [0] Bit
0x20 set.
1 = Not in data exchange state with the Status Register [0] bit 0x20 not set or
normal operation with the Status Register [0] bit 0x20 not set.
3 = Not in a defined state or in module state 1, 2 or 3.
4 = Normal operation with Status Register [0] bit 0x20 set
PROFIBUS Input Counter: Word 212
Input counter is incremented each time the input data is updated.
PROFIBUS Output Counter: Word 213
Output counter is incremented each time the output data is updated.
PROFIBUS Reserved Words: Word 214 to Word 219
Reserved for future use.
Last Global Command: Word 220
The value of the last global command code received from the master.
Bit
Designation
Significance
0
Reserved
1
Clear_Data
With this command the ASCI output data is deleted in data
transfer buffer and is changed to next transfer data buffer
contents.
2
Unfreeze
With 'Unfreeze': freezing input data is cancelled.
3
Freeze
The ASCI input data is fetched from next transfer buffer to data
transfer buffer and frozen. New input data is not fetched again
until the master sends the next 'Freeze' command.