beautypg.com

Download the project to the module, Download, Project – ProSoft Technology MVI56-PDPS User Manual

Page 36: To the module, 8 download the project to the module

background image

MVI56-PDPS ♦ ControlLogix Platform

Configuring the Module with RSLogix 5000

Profibus DP Slave Communication Module

Page 36 of 88

ProSoft Technology, Inc.

April 22, 2008

Byte Bit

Position

Designation

7 6 5 4 3 2 1 0

1

WD_Fact_1

2

WD_Fact_2

3

MinTSDR

4

Ident_Number_High

5

Ident_Number_Low

6

Group_Ident

7

Spec_User_Prm_Byte

8 to 243

User_Prm_Data

Byte 7

Spec_User_Prm_Byte

Bit Name

Significance

Default

State

0

Dis_Startbit

The start bit monitoring in the receiver
is switched off with this bit

Dis_Startbit = 1,
That is, start bit monitoring is switched off.

1

Dis_Stopbit

Stop bit monitoring in the receiver is
switched off with this bit

Dis_Stopbit = 0
That is, stop bit monitoring is not switched
off.

2

WD_Base

This bit specifies the time base used
to clock the watchdog.
WD_Base = 0: time base 10 ms
WD_Base = 1: time base 1 ms

WD_Base = 0
That is, the time base is 10 ms.

3 to 4

Res

To be parameterized with 0

0

5

Publisher_Enable

DXB-publisher-functionality of the
SPC3 is activated with this bit

Publisher_Enable = 0, DXB-request-
telegrams are ignored;
Publisher_Enable = 1, DXB-request-
telegramme are processed

6 to 7

Res

To be parameterized with 0

0

2.8

Download the Project to the Module

In order for the module to use the settings you configured, you must download
(copy) the updated Project file from your PC to the module.

To Download the Project File

1

In the tree view in ProSoft Configuration Builder, click once to select the
MVI56-PDPS module.

This manual is related to the following products: