MVI56-PDPS ♦ ControlLogix Platform
Configuring the Module with RSLogix 5000
Profibus DP Slave Communication Module
Page 36 of 88
ProSoft Technology, Inc.
April 22, 2008
Byte Bit
Position
Designation
7 6 5 4 3 2 1 0
1
WD_Fact_1
2
WD_Fact_2
3
MinTSDR
4
Ident_Number_High
5
Ident_Number_Low
6
Group_Ident
7
Spec_User_Prm_Byte
8 to 243
User_Prm_Data
Byte 7
Spec_User_Prm_Byte
Bit Name
Significance
Default
State
0
Dis_Startbit
The start bit monitoring in the receiver
is switched off with this bit
Dis_Startbit = 1,
That is, start bit monitoring is switched off.
1
Dis_Stopbit
Stop bit monitoring in the receiver is
switched off with this bit
Dis_Stopbit = 0
That is, stop bit monitoring is not switched
off.
2
WD_Base
This bit specifies the time base used
to clock the watchdog.
WD_Base = 0: time base 10 ms
WD_Base = 1: time base 1 ms
WD_Base = 0
That is, the time base is 10 ms.
3 to 4
Res
To be parameterized with 0
0
5
Publisher_Enable
DXB-publisher-functionality of the
SPC3 is activated with this bit
Publisher_Enable = 0, DXB-request-
telegrams are ignored;
Publisher_Enable = 1, DXB-request-
telegramme are processed
6 to 7
Res
To be parameterized with 0
0
2.8
Download the Project to the Module
In order for the module to use the settings you configured, you must download
(copy) the updated Project file from your PC to the module.
To Download the Project File
1
In the tree view in ProSoft Configuration Builder, click once to select the
MVI56-PDPS module.