MVI56-PDPS ♦ ControlLogix Platform

Diagnostics and Troubleshooting

Profibus DP Slave Communication Module

Page 54 of 88

ProSoft Technology, Inc.

April 22, 2008

Indicator Color

Status Indication

On

The LED is on when the module is communicating
over the backplane. Under normal operation, the LED
should blink rapidly on and off.

BP ACT

Amber

Off

The LED is off when the module is unable to
communicate with the processor. The processor is
either absent or not running.

Red

Off

The battery voltage is OK and running.

BATT

On

The battery voltage is low or the battery is not present.
The battery LED will illuminate briefly upon the first
installation of the module or if the unit has not had
power for an extended period of time. This behavior is
normal, however, should the LED come on in a
working installation, please contact ProSoft
Technology.

Off

The card is not receiving any power and is not
securely plugged into the rack.

Green

The module has passed its internal diagnostic tests
and is functional.

OK

Red / Green

Red

The module's diagnostics have detected an error, the
module is being configured, is not functioning
normally, or has not yet been able to initialize
backplane communication with the processor."

4.2.2 LEDs for the PROFIBUS Slave Port

ACTIVE ERROR

Description

Flashing On

PROFIBUS communication problem (not
receiving output)

Off On

Module configured and waiting for first output
data set.

Flashing together

Configuration

error during initialization.

Alternate

flashing

Watchdog timer expired.

On Off

Normal

operation.

On Rapid/irregular

flash

Configuration problem from master.

Off

Flashing

User timeout expired.

Off Off

Module not receiving power or program
terminated.