2.7 Set_Param

(SAP61)

ProSoft PROFIBUS Slave (PDPS) devices have a configurable parameter for
SPC3 User Prm Byte. The following illustrations show the value of this parameter
in Sycon, the configuration tool for ProLinx PROFIBUS Master devices, and in
ProSoft Configuration Builder for PROFIBUS, the configuration tool for ProSoft
PROFIBUS Master devices.

Parameter Data Structure

SPC3 evaluates the first seven data bytes (without user prm data), or the first
eight data bytes (with user prm data). The first seven bytes are specified
according to the standard. The eighth byte is used for SPC3-specific
communications. The additional bytes are available to the application.

Byte Bit

Position

Designation

7 6 5 4 3 2 1 0

0 Lock

Reg

Unio
Req

Sync
Req

Free
Req

WD
on

Res Res Res Station

status