Hardware specifications, Profibus slave port specifications – ProSoft Technology MVI56-PDPS User Manual
Page 56
MVI56-PDPS ♦ ControlLogix Platform
Reference
Profibus DP Slave Communication Module
Page 56 of 88
ProSoft Technology, Inc.
April 22, 2008
Configuration data obtained from configuration text file downloaded to
module. Sample configuration file included
Local or remote rack
5.1.3 Hardware
Specifications
Specification
Description
Backplane Current Load
800 mA @ 5 V DC
3mA @ 24V DC
Operating Temperature
0 to 60°C (32 to 140°F)
Storage Temperature
-40 to 85°C (-40 to 185°F)
Shock 30g
Operational
50g non-operational
Vibration: 5 g from 10 to 150 Hz
Relative Humidity
5% to 95% (non-condensing)
LED Indicators
Module Status
Backplane Transfer Status
Application Status
Serial Activity and Error LED Status
Debug/Configuration port (CFG)
CFG Port (CFG)
RJ45 (DB-9M with supplied cable)
RS-232 only
CIPconnect™ Ethernet routing using 1756-ENBT, 1756-
EN2T or similar
Shipped with Unit
RJ45 to DB-9M cables for each port
6-foot RS-232 configuration cable
5.1.4 PROFIBUS Slave Port Specifications
Type Specifications
General Parameters
Internal Database
400 registers (200 words) available
GSD File
Downloadable from ProSoft-Technology.com web site
PROFIBUS Slave
Communication parameters
Baud Rate: 9.6 kbps to 12 Mbps
Supported I/O length
122 words Input data
122 words Output data
200 words combined maximum
Supported PROFIBUS DP
features
Freeze Mode
Sync Mode
Auto Baud Setting
Configurable Parameters
a) PROFIBUS Node Address: 0 to 125
b) Data byte swapping
c) Action on loss of PROFIBUS connection
d) Comm Fail Timeout Multiplier