2.4 [MODULE]

The module section contains the data that applies to the whole module and
includes the backplane data transfer parameters.

[Module]

Module Name

: MVI56-PDPS Communication Module DEFAULT

The following table describes the content of this section:

[Section]/Item Value

Range

Description

[MODULE]

Configuration header for general module information

Module Name:

Up to 80
chars

Name of the module for use on reports. Use this
parameter to identify your module in your system.

2.5 [BACKPLANE]

The backplane section contains the data that applies to the backplane data
transfer parameters.

[Backplane]

Read Register Count : 122 #Number of words to move from MVI to Processor

(Profibus Output)

Write Register Count : 122 #Number of words to move from Processor to MVI

(Profibus Input)

[Section]/Item Value

Range

Description

[BACKPLANE]

Configuration header for general Backplane information

Read Register Count

122

0 to 122 Number of words to move from the PDPS Module to

controller tags in the processor (PROFIBUS Output)

Write Register Count

122

0 or 122 Number of words to move from controller tags in the

processor to the PDPS module (PROFIBUS Input)

2.6 [PROFIBUS

SLAVE]

The PROFIBUS Slave section contains the data that applies to the PROFIBUS
Slave parameters.

[Profibus Slave]

Slave Address : 6 #Profibus node address for slave (0-125)

Swap Input Bytes : No #Swap bytes in input image (Yes or No)

Swap Output Bytes : No #Swap bytes in output image (Yes or No)

Comm Failure Mode : 1 #0=x-fer on comm fail, 1=no x-fer on fail

Comm Timeout Multiplier : 1 #(1 to 10) * 125 mSec communication timeout

Use Database Paging : N # Y or N. Enables or disable paging.

2.6.1 Slave

Address

0 to 125

This manual is related to the following products: