MVI56-PDPS ♦ ControlLogix Platform

Reference

Profibus DP Slave Communication Module

Page 62 of 88

ProSoft Technology, Inc.

April 22, 2008

Each image has a defined structure depending on the data content and the
function of the data transfer as defined in the following topics:

5.2.5 Normal Data Transfer

Normal data transfer includes the paging of the user data found in the module's
internal database and the Status Data. These data are transferred through read
(input image) and write (output image) blocks. Refer to Module Configuration
for a description of the data objects used with the blocks. The structure and
function of each block is discussed in the following topics.

Read Block

These blocks of data transfer information from the module to the ControlLogix
processor, and transfer output (control) data sent to the module from the remote
master unit. The structure of the input image used to transfer this data is shown
in the following table:

Word Description

Length

0

Write Block ID

1

1 to 122

Read Data

122

123 to 201

Reserved

79

202

Program Scan Counter

1

203 to 206

Block Transfer Status

4

207 to 220

PDPS Status

14

221 to 248

Reserved

28

249

Read Block ID

1

Write Block

These blocks of data transfer information from the ControlLogix processor to the
module and source the input (monitored) data to be used by the remote master.
The structure of the output image used to transfer this data is shown in the
following table:

Word Description

Length

0

Write Block ID

1

1 to 122

PROFIBUS input data

122

123 to 200

Reserved

78

201 ti 247

Spare

47

5.2.6 Command Control Blocks

Command control blocks are special blocks used to control the module. The
current version of the software supports the following command control blocks.