beautypg.com

Cable connections – ProSoft Technology MVI56-DFCM User Manual

Page 97

background image

MVI56-DFCM ♦ ControlLogix Platform

Reference

DF1 Half/Full Duplex Master/Slave Serial Communication Module

User Manual

ProSoft Technology, Inc.

Page 97 of 106

September 24, 2014

5.4.4 Module Specific Error (not DFCM Compliant)

Code (Int)

Code (Hex) Description

-1

0xFFFF

CTS modem control line not set before transmit

-2

0xFFFE

Timeout while transmitting message

-10

0xFFF6

Timeout waiting for DLE-ACK after request

-11

0xFFF5

Timeout waiting for response after request

-12

0xFFF4

Reply data does not match requested byte count

-20

0xFFEC

DLE-NAK received after request

-21

0xFFEB

DLE-NAK sent after response

-200

0xFF38

DLE-NAK received after request

5.5

Cable Connections

The application ports on the MVI56-DFCM module support RS-232, RS-422, and
RS-485 interfaces. Please inspect the module to ensure that the jumpers are set
correctly to correspond with the type of interface you are using.

Note: When using RS-232 with radio modem applications, some radios or modems require

hardware handshaking (control and monitoring of modem signal lines). Enable this in the

configuration of the module by setting the UseCTS parameter to 1.

5.5.1 RS-232 Configuration/Debug Port

This port is physically an RJ45 connection. An RJ45 to DB-9 adapter cable is
included with the module. This port permits a PC-based terminal emulation
program to view configuration and status data in the module and to control the
module. The cable pinout for communications on this port is shown in the
following diagram.