MVI56-DFCM ♦ ControlLogix Platform
Reference
DF1 Half/Full Duplex Master/Slave Serial Communication Module
User Manual
ProSoft Technology, Inc.
Page 97 of 106
September 24, 2014
5.4.4 Module Specific Error (not DFCM Compliant)
Code (Int)
Code (Hex) Description
-1
0xFFFF
CTS modem control line not set before transmit
-2
0xFFFE
Timeout while transmitting message
-10
0xFFF6
Timeout waiting for DLE-ACK after request
-11
0xFFF5
Timeout waiting for response after request
-12
0xFFF4
Reply data does not match requested byte count
-20
0xFFEC
DLE-NAK received after request
-21
0xFFEB
DLE-NAK sent after response
-200
0xFF38
DLE-NAK received after request
5.5
Cable Connections
The application ports on the MVI56-DFCM module support RS-232, RS-422, and
RS-485 interfaces. Please inspect the module to ensure that the jumpers are set
correctly to correspond with the type of interface you are using.
Note: When using RS-232 with radio modem applications, some radios or modems require
hardware handshaking (control and monitoring of modem signal lines). Enable this in the
configuration of the module by setting the UseCTS parameter to 1.
5.5.1 RS-232 Configuration/Debug Port
This port is physically an RJ45 connection. An RJ45 to DB-9 adapter cable is
included with the module. This port permits a PC-based terminal emulation
program to view configuration and status data in the module and to control the
module. The cable pinout for communications on this port is shown in the
following diagram.