ProSoft Technology MVI56-DFCM User Manual
Page 46

Ladder Logic
MVI56-DFCM ♦ ControlLogix Platform
User Manual
DF1 Half/Full Duplex Master/Slave Serial Communication Module
Page 46 of 106
ProSoft Technology, Inc.
September 24, 2014
This action opens the Select Module dialog box:
2 Select the 1756-M
ODULE
(G
ENERIC
1756
M
ODULE
) from the list and click OK.
This action opens the New Module dialog box.
3 Enter the Name, Description and Slot options for your application. You must
select the Comm Format as D
ATA
-
INT in the dialog box, otherwise the
module will not communicate. Click OK to continue.
Parameter
Value
Name
Enter a module identification string. Example: DFCM_2
Description
Enter a description for the module. Example: DF1
H
ALF
/F
ULL
D
UPLEX
M
ASTER
/S
LAVE
S
ERIAL
C
OMMUNICATION
M
ODULE
Comm Format
Select D
ATA
-INT.
Slot
Enter the slot number in the rack where the MVI56-DFCM
module is located.
Input Assembly Instance
1
Input Size
250
Output Assembly Instance
2
Output Size
248
Configuration Assembly Instance
4
Configuration Size
0