ProSoft Technology MVI56-DFCM User Manual
Page 84

Reference
MVI56-DFCM ♦ ControlLogix Platform
User Manual
DF1 Half/Full Duplex Master/Slave Serial Communication Module
Page 84 of 106
ProSoft Technology, Inc.
September 24, 2014
Master Command List Data Blocks (6000 to 6004 and 6100 to 6104)
Each port on the module can be configured as a DF1 Master device containing
its own list of one hundred commands. The commands are sent from the
processor using Write Block ID’s 6000 to 6004 for DF1 Port 1 and 6100 to 6104
for DF1 Port 2. The module will sequentially request each block from the
processor. Ladder logic handles the data transfers. The structure of each block is
shown below:
Offset
Description
Length
0
6000 to 6004 and 6100 to 6104
1
1 to 12
Command Definition
12
13 to 24
Command Definition
12
25 to 36
Command Definition
12
37 to 48
Command Definition
12
49 to 60
Command Definition
12
61 to 72
Command Definition
12
73 to 84
Command Definition
12
85 to 96
Command Definition
12
97 to 108
Command Definition
12
109 to 120
Command Definition
12
121 to 132
Command Definition
12
133 to 144
Command Definition
12
145 to 156
Command Definition
12
157 to 68
Command Definition
12
169 to 180
Command Definition
12
181 to 192
Command Definition
12
193 to 204
Command Definition
12
205 to 216
Command Definition
12
217 to 228
Command Definition
12
229 to 240
Command Definition
12
241 to 247
Spare
7
5.2.5 Event Command Blocks (1000 or 2000)
Event Command Blocks send DF1 commands directly from the ladder logic to
one of the Master ports. The Event Command Write Block format is:
Offset
Description
Length
0
1000 (Send from Port 1) or 2000 (Send from Port 2)
1
1
Internal DB Address
1
2
Point Count
1
3
Swap Code
1
4
Node Address
1
5
Function Code
1
6
Parameter #1
1