ProSoft Technology MVI56-DFCM User Manual
Page 51

MVI56-DFCM ♦ ControlLogix Platform
Diagnostics and Troubleshooting
DF1 Half/Full Duplex Master/Slave Serial Communication Module
User Manual
ProSoft Technology, Inc.
Page 51 of 106
September 24, 2014
The bits in each configuration word are shown below. The module configuration
error word has the following definition:
Bit
Description
Value
0
Read block start value is greater that the database size.
0x0001
1
Read block start value is less than zero.
0x0002
2
Read block count value is less than zero.
0x0004
3
Read block count + start is greater than the database size.
0x0008
4
Write block start value is greater that the database size.
0x0010
5
Write block start value is less than zero.
0x0020
6
Write block count value is less than zero.
0x0040
7
Write block count + start is greater than the database size.
0x0080
8
0x0100
9
0x0200
10
0x0400
11
0x0800
12
0x1000
13
0x2000
14
0x4000
15
0x8000
The port configuration error words have the following definitions:
Bit
Description
Value
0
Type code is not valid. Enter a value from 0 (Master) to 1 (slave).
0x0001
1
Protocol parameter is not valid.
0x0002
2
Termination type parameter is not valid.
0x0004
3
Baud rate parameter is not valid.
0x0008
4
Parity parameter is not valid.
0x0010
5
Data bits parameter is not valid.
0x0020
6
Stop bits parameter is not valid.
0x0040
7
Command count parameter is not valid.
0x0080
8
Retry count parameter is not valid.
0x0100
9
Invalid Override File Map Count
0x0200
10
Spare
0x0400
11
Spare
0x0800
12
Spare
0x1000
13
Spare
0x2000
14
Spare
0x4000
15
Spare
0x8000